Technical data

Description
3.1 Area of application and properties
RS 485 Repeater
10 Manual, 02/2011, A5E03382072-01
Rules
If you set up a PROFIBUS network with RS 485 repeaters:
The number of RS 485 repeaters in series must be configured in STEP 7.
Up to nine RS 485 repeaters may be connected in series.
The maximum cable length between two nodes with RS 485 repeater may not exceed the
values listed in the table below.
Table 3- 2 Maximum cable length between two RS 485 repeaters
Transmission rate Maximum cable length between 2 nodes (in m) with RS 485 repeater
9.6 to 187.5 kbps 10000
500 kbps 4000
1.5 Mbps 2000
3 to 12 Mbps 1000