Technical data

Active components
4.4 Active components for interfacing to PROFIBUS PA
PROFIBUS Network Manual
92 System Manual, Edition 04/2009, C79000-G8976-C124-03
([
DP/PA coupler
Hazardous (Ex) area
"Programming, operating and
monitoring"
SIMATIC PCS 7 or third-party tool for
parameter assignment
PDM or other tool for parame-
ter assignment
Cell level
Field level
Management
level
DP/PA coupler Ex (i)
Industrial Ethernet
PROFIBUS-DP
PROFIBUS-PA
ET 200X
DP-Master
Figure 4-18 Logical integration of DP/PA couplers into the system
For more information on expanding the PA line, refer to section "Field distributors AFD/AFS
(Page
97)"
Areas of application of the DP/PA coupler
The DP/PA coupler is available in two versions:
DP/PA coupler Ex [ia]: You can attach all field devices that are certified for
PROFIBUS PA and that are inside the hazardous area.
DP/PA coupler FDC 157-0: You can attach all field devices that are certified for
PROFIBUS PA and that are outside the hazardous area.
The DP/PA coupler is "related equipment" in compliance with EN 50014 or EN 50020.
Properties of the DP/PA coupler (general)
The DP/PA coupler FDC 157-0 (6ES7 157-0AC83-0XA0) has the following characteristics:
Electrical isolation between PROFIBUS DP and PROFIBUS PA
Conversion of the physical transmission properties between RS485 and IEC 611582
Diagnostics using LEDs
Transmission speed on PROFIBUS DP 45.45 kbps
Transmission speed on PROFIBUSPA 31.25 kbps
Integrated power supply unit