Technical data

Passive Components for PROFIBUSPA
8.1 SIMATIC NET cables for PROFIBUS PA
PROFIBUS Network Manual
228 System Manual, Edition 04/2009, C79000-G8976-C124-03
Table 8- 1 Bus cables for PROFIBUS PA
Technical specifications
1)
Cable type
FC process cable for PROFIBUS PA
3) 2)
Order no. 6XV1 830-5EH10
6XV1 830-5FH10
Attenuation
at 16 MHz
at 4 MHz
at 38.4 kHz
at 9.6 kHz
-
-
≤ 3 dB/km
-
Surge impedance
at 9.6 kHz
at 31.25 kHz
at 38.4 kHz
at 3 to 20 MHz
Rated value
-
100 ± 20 Ω
100 ± 20 Ω
-
100 Ω
Loop resistance 22 Ω/km
Shield resistance 6.5 Ω
Effective capacitance at 1 kHz
Wire-wire
Wire-shield
50 nF/km
90 nF/km
Operating voltage (rms value) 100 V
Continuous current of the power wires at 25
°C
-
Cable type standard code 02Y SY (ST)CY 1x2x1.0/2.55-100 BL/SW OE FR
Jacket
Material
Color
Diameter
PVC
blue / black
8.0 ± 0.4 mm
Wires
Conductor cross section
Color of the wire insulation
0.83 mm
2
(AWG18)
Red/green
Perm. ambient conditions
-Operating temperature
-Transportation/storage temperature
-Installation temperature
-40°C + 80°C
-40°C + 80°C
-20°C + 80°C
Bending radiuses
Single bend
Multiple bends
40 mm
80 mm
Max. tensile load 150 N
Approx. weight 103 kg/km
Resistance to fire Flame retardant to IEC 60332-3-24
Resistance to oil Resistant to mineral oils and grease
UV resistance Yes