Technical data
Passive Components for PROFIBUSPA
8.1 SIMATIC NET cables for PROFIBUS PA
PROFIBUS Network Manual
228 System Manual, Edition 04/2009, C79000-G8976-C124-03
Table 8- 1 Bus cables for PROFIBUS PA
Technical specifications
1)
Cable type
FC process cable for PROFIBUS PA
3) 2)
Order no. 6XV1 830-5EH10
6XV1 830-5FH10
Attenuation
• at 16 MHz
• at 4 MHz
• at 38.4 kHz
• at 9.6 kHz
• -
• -
• ≤ 3 dB/km
• -
Surge impedance
• at 9.6 kHz
• at 31.25 kHz
• at 38.4 kHz
• at 3 to 20 MHz
• Rated value
• -
• 100 ± 20 Ω
• 100 ± 20 Ω
• -
• 100 Ω
Loop resistance 22 Ω/km
Shield resistance 6.5 Ω
Effective capacitance at 1 kHz
• Wire-wire
• Wire-shield
• 50 nF/km
• 90 nF/km
Operating voltage (rms value) 100 V
Continuous current of the power wires at 25
°C
-
Cable type standard code 02Y SY (ST)CY 1x2x1.0/2.55-100 BL/SW OE FR
Jacket
• Material
• Color
• Diameter
• PVC
• blue / black
• 8.0 ± 0.4 mm
Wires
• Conductor cross section
• Color of the wire insulation
• 0.83 mm
2
(AWG18)
• Red/green
Perm. ambient conditions
• -Operating temperature
• -Transportation/storage temperature
• -Installation temperature
• -40°C + 80°C
• -40°C + 80°C
• -20°C + 80°C
Bending radiuses
• Single bend
• Multiple bends
• 40 mm
• 80 mm
Max. tensile load 150 N
Approx. weight 103 kg/km
Resistance to fire Flame retardant to IEC 60332-3-24
Resistance to oil Resistant to mineral oils and grease
UV resistance Yes