Technical data
Passive components for optical networks
7.3 Glass FO cables
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
209
Cable type Flexible fiberoptic
Trailing cable (62.5/125 μm)
Order no. 6XV1 820-6AH10
Cable design Splittable outdoor cable
Core type Hollow core, filled
Materials basic element PUR, black
Strain relief GFK central element, Aramid yarn
Outer jacket/
Wire color
PUR, black
Dimensions of basic element (3.5 ± 0.2) mm
Outer dimensions 13.4 ± 0.4 mm
Cable weight Approx. 135 kg/km
Permitted tensile force ≤ 2000 N (in operation)
≤ 1000 N (brief)
Bending radiuses 150 mm
max. 100,000 bending cycles
Installation temperature -5°C to +50°C
Operating temperature -30°C to +60°C
Storage temperature -30°C to +70°C
Resistance to fire -
Free of halogens No
Silicone-free Yes
ROHS-compliant Yes
UL approval No
Shipbuilding approval No
1)
With copper cores and no load
2)
With copper cores and maximum load (6 A)
Table 7- 17 Technical specifications of the fiber-optic standard cable GP and fiber-optic ground cable
Cable type Fiber-optic standard cable GP
(50/125 μm)
Fiber-optic ground cable
(50/125 μm)
Order no. 6XV1 873-2A 6XV1 873-2G
Area of application Universal cable for use indoors and
outdoors
Longitudinally and laterally watertight
cable for use outdoors with non-
metallic rodent protection for direct
underground installation
How supplied Sold by the meter; pre-assembled with
4 BFOC connectors
Sold by the meter; pre-assembled with
4 BFOC connectors
Cable type
(Standard code)
AT-W(ZN)YY 2x1G50/125 AT-WQ(ZN)Y(ZN)B2Y 2G50/125
Fiber type Multimode graded-index fiber
50/125 µm
Multimode graded-index fiber
50/125 µm