Technical data

Passive components for optical networks
7.2 Plastic and PCF fiber-optic cable
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
201
The cable can be ordered both in meters and as a preassembled cable. Cables for devices
with an integrated optical interface are fitted with 2 x 2 simplex connectors, cables for
connection of OLM/P11 and OLM/P12 have 2 x 2 BFOC connectors. The cables are
supplied with a pulling loop at one end that allows the cables to be pulled, for example, into
cable channels.
Properties
The PCF standard cable GP is
Designed for 100 N permanent tensile strain
Conditionally resistant to mineral oil ASTM no. 2
Conditionally resistant to greases
UV resistant
Flame retardant to IEC 60332-1
Equally suitable for PROFIBUS and PROFINET (outer jacket green)
Use
The PCF standard cable GP 6XV1 861-2A/3A/7A *** is a robust round cable for use indoors
and outdoors with cable lengths up to 400 m (OLM) or 300 m (integrated optical interfaces,
OBT) in each case between two nodes.
Table 7- 9 Ordering data: In meters and preassembled PCF fiberoptic cables for OLM/P
Ordering data
PROFIBUS PCF Standard Cable GP 200/230
I V(ZN)YY 2K200/230
Sold by the meter; max. length 2,000 m; minimum
order 20 m
6XV1 861-2A
PCF fiber-optic cable with 2 cores, PVC outer
jacket, for bridging large distances up to 400 m,
preassembled with 2x2 BFOC male connectors,
Outer jacket stripped over 20 cm at both ends
and pulling loop at one end,
for connection of OLM/P.
* other lengths on request
Preferred lengths*
75 m
100 m
150 m
200 m
250 m
300 m
400 m
6XV1 861-3AN75
6XV1 861-3AT10
6XV1 861-3AT15
6XV1v861-3AT20
6XV1 861-3AT25
6XV1 861-3AT30
6XV1 861-3AT40