Technical data

Passive components for optical networks
7.2 Plastic and PCF fiber-optic cable
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
193
Description PCF standard cable GP PCF trailing cable PCF trailing cable GP
Maximum permitted tensile
strain
Brief/permanent
100 N 800 N
Permitted ambient conditions
Transportation/storage
temperature
Installation temperature
Operating temperature
-25°C to 75°C
-5°C to 50°C
-25°C to 75°C
-25°C to 75°C
-5°C to 50°C
-30°C to 75°C
Resistant to
mineral oil ASTM no. 2,
grease or water
UV radiation
conditional
1
conditional
1
Yes
Silicone-free Yes Yes Yes
ROHS-compliant Yes Yes Yes
Resistance to fire Flame retardant to IEC 60332-1
Outer dimensions 7.2 mm 8.8 mm
Weight 45 kg/km 85 kg/km
UL/CSA approval OFN
(NEC Article 770, UL1651)/
OFN, 90°C, FT1, FT4 (CSA-
Standard C22.2 No232-
M1988)
- OFN
(NEC Article 770, UL1651)/
OFN, 90°C, FT1, FT4 (CSA-
Standard C22.2 No232-
M1988)
1
Please ask your Siemens contact about specific applications.