Technical data

Passive components for optical networks
7.2 Plastic and PCF fiber-optic cable
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
191
Properties of fiberoptic cables
Use Siemens plastic and PCF fiber-optic cables with the following features:
Table 7- 2 Properties of fiberoptic cables
Description Plastic fiber-optic duplex
core
Plastic fiber-optic standard
cable
PCF fiber-optic standard
cable
Order no. 6XV1 821-2AN50 6XV1 821-0AH10 6XV1 821-1BN75
Standard code I-VY2P 980/1000 150A I-VY4Y2P 980/1000 160A I-VY2K 200/230
10A17+8B20
Area of application Used indoors in areas
where little mechanical load
is expected, such as in
laboratory setups or in
cubicles
For indoor use with cable
lengths up to 80 m
For indoor use with cable
lengths up to 300 m
Only available preassembled
with BFOC or simplex
connectors
Cable length between
OLM - OLM
Integrated optical
interfaces, OBT
50 m
50 m
80 m
50 m
400 m
300 m
Fiber Type Step-index cable
Core diameter 980 μm 200 μm
Core material Polymethyl methacrylate (PMMA) Fused silica
Cladding outer diameter 1000 μm 230 μm
Cladding material Fluoridated special polymer
Inner jacket
Material
Color
Diameter
PVC
gray
2.2 ± 0.01 mm
PA
black and orange
2.2 ± 0.01 mm
-
(without inner jacket)
-
Outer jacket
Material
Color
-
-
PVC
Purple
PVC
Purple
Number of fibers 2
Attenuation at wavelength ≤ 230 dB/km
660 nm
≤ 10 dB/km
660 nm
Strain relief - Kevlar fibers Kevlar fibers
Maximum permitted tensile
strain
brief
Continuous
≤ 50 N
not suitable for
continuous tensile load
≤ 100 N
not suitable for
continuous tensile load
≤ 500 N
≤ 100 N
(only on strain relief, ≤ 50
N on plug or single core)
Permitted ambient conditions
Transportation/storage
temperature
Installation temperature
Operating temperature
-35 °C to +85 °C
0 °C to +50 °C
-30 °C to +70 °C
-30 °C to +70 °C
0 °C to +50 °C
-30 °C to +70 °C
-20 °C to +70 °C
-5 °C to +50 °C
-20 °C to +70 °C