Technical data

Bus connectors and preassembled cables
6.4 D-sub bus connector with screw terminals
PROFIBUS Network Manual
162 System Manual, Edition 04/2009, C79000-G8976-C124-03
Fitting the bus connector
Points to note about installing the bus connector with axial cable outlet (order number
6GK1 500-0EA02):
Strip both cable ends as shown in the figure below with the FastConnect stripping tool
(sizes and lengths are shown in the table on the rear of the tool).
6,(0(16

%
$
Figure 6-18 Preparing the ends of the cable for the bus connector with axial cable outlet
Undo the screws in the casing and remove the cover.
Feed the wires into the terminals of the screw terminal blocks.
Press the cable jacket between the two clip bars.
Make sure that the cable shields are lying on the metal guide.
When you connect to the screw terminals, the stranded cores must be fitted with wireend
ferrules (0.25 mm
2
complying with DIN 46228).
Make sure that the braid shield lies on the contact surfaces of the connector.
Replace the cover and screw it tight.
Activate the terminating resistor if the bus connector is at the end of a segment.
Note
Stranded cores must only be used in screw terminals with wireend ferrules fitted (0.25
mm
2
complying with DIN 46228). Use only wireend ferrules made of materials with
permanently stable contact properties, for example copper with a tinplated surface (not
aluminum).