Technical data
Bus connectors and preassembled cables
6.4 D-sub bus connector with screw terminals
PROFIBUS Network Manual
162 System Manual, Edition 04/2009, C79000-G8976-C124-03
Fitting the bus connector
Points to note about installing the bus connector with axial cable outlet (order number
6GK1 500-0EA02):
● Strip both cable ends as shown in the figure below with the FastConnect stripping tool
(sizes and lengths are shown in the table on the rear of the tool).
6,(0(16
%
$
Figure 6-18 Preparing the ends of the cable for the bus connector with axial cable outlet
● Undo the screws in the casing and remove the cover.
● Feed the wires into the terminals of the screw terminal blocks.
● Press the cable jacket between the two clip bars.
● Make sure that the cable shields are lying on the metal guide.
● When you connect to the screw terminals, the stranded cores must be fitted with wireend
ferrules (0.25 mm
2
complying with DIN 46228).
● Make sure that the braid shield lies on the contact surfaces of the connector.
● Replace the cover and screw it tight.
● Activate the terminating resistor if the bus connector is at the end of a segment.
Note
Stranded cores must only be used in screw terminals with wireend ferrules fitted (0.25
mm
2
complying with DIN 46228). Use only wireend ferrules made of materials with
permanently stable contact properties, for example copper with a tinplated surface (not
aluminum).