Technical data
Cables for PROFIBUS RS485 networks
5.4 FCFRNC cable (bus cable with halogenfree outer jacket)
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
121
The structure of the cable allows the use of the FastConnect (FC) stripping tool for fast
stripping of the cable (see Section
Installation instructions for SIMATIC NET PROFIBUS
FAST CONNECT (Page
138))
Properties
PROFIBUS FC standard cable with blue outer jacket for use in hazardous areas with
ET 200iSP.
Due to the composition of the jacket material, the bus cable has the following characteristics:
● Flameretardant
● Selfextinguishing in case of fire
● Conditionally resistant to mineral oils and fats
● Sheath material not free of halogens
Use
The bus cable is intended for fixed installation in buildings (inhouse cabling).
5.4 FCFRNC cable (bus cable with halogenfree outer jacket)
,QQHUFRQGXFWRU
VROLGFRSSHU
7LQSODWHGFRSSHUEUDLG
VKLHOG
$OXPLQXPIRLO
,QVXODWLRQ
VOHHYH
FHOOXODU3(
)51&RXWHUMDFNHW
3ODVWLFIRLO
)51&ILOOHU
Figure 5-3 Structure of the bus cable with halogenfree outer jacket
Bus cable with halogenfree outer jacket 6XV1 830-0LH10
The bus cable with a halogenfree outer jacket 6XV1 8300LH10 complies with the
specification IEC 61158-2 / EN 61158-2, cable type A, with solid copper cores (AWG 22).
The structure of the cable allows the use of the FastConnect (FC) stripping tool for fast
stripping of the PROFIBUS cable, see Section
Installation instructions for SIMATIC NET
PROFIBUS FAST CONNECT (Page
138).