User Manual
Building Technologies / HVAC Products CE1G2727en 23.03.2005 1/5
G2727
en
Installation and commissioning guide
Temperature controller
Multi-zone ducted systems
RRV856
Function summary
• The RRV856 controller is designed for ducted HVAC
systems.
• The AC system is divided into zones (2-6 zones) by the
on/off control of the damper actuators. The default unit
for zone 1 is the QAX850 master room unit with
QAW850 zone room units used for additional zone.
• Wall units measure zone temperatures and evaluate the
demand for each zone based on the corresponding
zone setpoint. The zone damper opens on demand
from its corresponding zone room unit and closes when
there is no demand.
• Heating/cooling output and fan speed is determined
based on total demand from all zones.
Installation
Place of installation
• Mounting choices:
− Control cabinet
− Control panel
− Side of FCU
− Wall, ceiling space, cupboard
• Easy access is required for service personnel.
• The controller should not be freely accessible by build-
ing occupants.
• Do not install outside without suitable weather protec-
tion.
• Permissible ambient temperature: 0...50°C.
Electrical installation
• The local regulations for electrical installations must be
observed.
• Cable restraints must be used for the wires to terminals L,
N, Q... (AC230V).
• Cable restraints should be used for all wiring to avoid
disconnection (see diagram below).
80160
Permissible cable lengths
• For all field devices: room unit, sensors
− max. 60 m where A ≥ 0.5 mm
2
− max. 100 m where A ≥ 1.0 mm
2
• Signal cable type
− 2-wire standard installation cable (unshielded)
− Bus topology is free configuration. Ring, star etc.
− Twisted pair (unshielded) is recom-
mended for enhanced immunity to external electro-
magnetic interference, for example, in the vicinity of
radio transmitters or frequency converters.
• RRV856 controller can be mounted in any orientation.
• Ensure adequate air circulation to dissipate heat gener-
ated during operation.
DIN rail mounting
1. The housing rail is designed for snap mounting on DIN
rails, type EN50022-35 X 7.5
Surface mounting
1. Hold controller against the surface.
2. Mark fixing holes on the wall.
3. Drill holes.
4. Screw controller to the surface.
5. When mounting controller to a FCU, take care not to
damage internal components. E.g. Drilling through
coils.
Terminal covers
• The covers will provide IP30 protection when surface
mounting on wall or FCU. IP20 without terminal covers.
• The terminal covers include screws for fixing to control-
ler and knock-out holes for cable entry.