The RMZ792 bus operator unit does not allow for commissioning (configuring) the
devices in the KNX network. Commissioning must occur locally on the device in the
KNX network using the RMZ790 or RMZ791 operator units or centrally using the
OCI700.1 service tool.
Name Figure Function Type Data
sheet
Service tool
OCI700 interface and
PC software ACS790
for commissioning,
service, and operation
OCI700.1
N5655
1.3 KNX network
The following figure shows a simple KNX network with an RMZ792 bus operator unit in
area 1 (fixed connection) and line 1 (mobile use).
RMZ792 Bus operator unit
RM.. Synco 700 controller
RMB..
Synco 700 control unit
QAW740
Synco 700 room unit
RXB2..
Room controller
OZW..
Central communication unit
RDG..
Room thermostats for wall mounting
RDF.. / RDU..
Room thermostats for partial wall mounting
N140/13
Area/line coupler
The bus operator unit can be used to operate bus devices, i.e. KNX network devices.
The bus devices can be integrated in one or several lines. For networks with several
lines, access is possible to devices of neighboring lines or areas regardless of the
connection location.
We recommend to place the operator unit within the line or the area of the bus device
to be operated to keep down bus load.
OCI700 service tool
Use of the RMZ792 bus
operator unit