Basic Documentation

38/58
Siemens Bus operator unit RMZ792 Series B CE1P3113en
Building Technologies 7 Data backup 07.07.2011
7.4 Troubleshooting
Faults Cause / Solution
Save Failed
Progress ----%
Setting not saved
Second device has invalid address.
Communications interrupted to
second unit.
Solution:
Check bus connection and address of
the second device.
Back up data again.
Save Failed
Progress 1…99%
Settings incompletely saved
Communications or power supply
interrupted while data is backed up to
second device.
Solution:
Check bus connection and power
supply.
Back up data again.
Restore Failed
Settings not restored
No new start of bus operator unit
Second device has invalid address.
Communications interrupted to
second device.
Solution:
Check bus connection and address of
the second device.
Restore data again.
Restore Failed
Settings incompletely restored, device
list has been deleted
New start of bus operator unit
Corrupt backup data.
Software version incompatible with
backup data.
Communications or power supply
interrupted while data is restored from
second device.
Solution:
Check bus connection and power
supply.
Use consistent and compatible
backup file.
Restore data again.
Possible cases