Basic Documentation
28/58
Siemens Bus operator unit RMZ792 Series B CE1P3113en
Building Technologies 6 "Commissioning" menu 07.07.2011
6.3.4 "List information" submenu
Display detailed information on the current status of the device list.
Main menu > Commissioning > Device list > List information
Operating line Range Factory setting
State of list See below
List error See below
Number of devices current 0…150
State of list and List error:
State of list Description
Acquired Device list created or devices were added.
Address invalid Device search interrupted. The device list is
invalid and must be recreated.
Deleted Device list empty.
List error Description
--- No error. The device list is OK.
Address twice The device list contains several devices with
identical device address. Eliminate the
address conflict.
List complete The list is full (150 entries).
The current number of devices in the device list is displayed by the value Number of
devices current.
6.3.5 "Delete list" submenu
Delete the entire device list.
Main menu > Commissioning > Device list > Delete list
Operating line Range Factory setting
Delete list… --- / Deleted ---
The device list along with device names is deleted if you press the OK button following
a confirmation message. In addition, all Favorites pages are deleted.
Confirmation message: You can stop deletion by pressing the ESC button before
pressing the OK button.
Application
Operating lines
Application
Operating line