Basic Documentation
87/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 6 Boiler temperature control 2017-09-29
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Checkback signal burner
Operating line
Range
Factory setting
Signal delay start
00.05…59.55 m.s
04.00 m.s
Signal interruption operation
00.00…59.55 m.s
20.00 m.s
Impact of fault
No stop / Stop
Stop
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Overload pump
Operating line
Range
Factory setting
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
and reset
Fault acknowledgement B None / Acknowledge /
Acknowledge and reset
Acknowledge
and reset
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Fault input 1
Operating line
Range
Factory setting
Fault text
Max. 20 characters
Water shortage
Impact of fault
No stop / Stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status message delay
00.00…59.55 m.s
00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Fault input 2
Operating line
Range
Factory setting
Fault settings
Max. 20 characters
Overpressure
Impact of fault
No stop / Stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status message delay 00.00…59.55 m.s 00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Fault input 3
Operating line
Range
Factory setting
Fault settings
Max. 20 characters
Underpressure
Impact of fault
No stop / Stop
Stop
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status message delay
00.00…59.55 m.s
00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Flue temp supervision
Operating line
Range
Factory setting
Flue gas temperature limit value
---- / 8…400 °C
---- °C
Impact of fault
No stop / Stop
No stop
Fault priority
Urgent / Not urgent
Nonurgent