Basic Documentation

52/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 5 General functions, fundamentals 2017-09-29
This setting can only be made on plant with no boiler.
Every heat consumer has a minimum overrun time of 60 seconds.
With DHW heating, it is to be noted that discharging protection is given priority over
pump overrun.
In the case of DHW heating with primary and secondary pump, the secondary pump
operates for an additional pump overrun time to prevent the external heat exchanger
from reaching excessive temperatures.
Main menu > Settings > DHW > Controller primary circuit
Operating line
Range
Factory setting
Overrun time secondary pump
0…60 min
1 min
5.5 Pump kick and valve kick
Main menu > Commissioning > Settings > … or
Main menu > Settings > Protective functions
Operating line
Range
Factory setting
Kick day
MondaySunday
Monday
Kick time
00:00…23:59
10:00
Pump/valve kick --- / Pump + Valve /
Pump / Valve
Pump + valve
The pump kick or valve kick is a protective function that is carried out periodically. It
prevents pumps and / or valves from seizing after longer off periods (e.g. summer
operation). For the kick function to be performed, the pump or actuator must not have
been activated for at least one week.
To prevent the pumps and valves from seizing, a point in time can be defined where the
pumps are put into operation and the valves are driven to their fully open and fully
closed positions.
To be defined are the kick day and kick time. The function can be deactivated (pump /
valve kick = ---).
It can also be selected whether the function shall apply to pumps only, valves only, or
to both.
The selected setting will then apply to all pumps and valves connected to the
RMH760B. If a plant uses several RMH760B, the setting must be made on each of
them.
With the kick day and kick time settings, it is to be noted that these settings are also
used for automatic changeover of twin pumps (for more detailed information, refer to
section 5.8 "Pump control and twin pumps").
The kick time for pumps and actuators need not be set; it is fixed at 30 seconds.
If several pumps are present, they will be kicked one after the other. After the end of a
kick, the next pump will be kicked after an interval of 30 seconds.
The valve kick does not act on the boiler’s shutoff valve.
Notes