Basic Documentation
48/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 5 General functions, fundamentals 2017-09-29
For the circulating pump, following applies during the holiday period:
• If "Protection"
has been selected as the DHW operating mode during the holiday
period, the circulating pump will be deactivated
• In the other operating modes, the circulating pump will run according to the time
program
For the legionella function, following applies during the holiday period:
• If "Protection"
has been selected as the DHW operating mode during the holiday
period, the legionella function will be deactivated
• In the other operating modes, the legionella function will remain activated
Main menu > Heating circuit 1 (or 2 or 3) > Room operating mode
Operating line
Range
Factory setting
Room operating mode holidays
Economy
Economy
Protection
Main menu > DHW > DHW optg mode
Operating line
Range
Factory setting
DHW operating mode holidays
Auto
Protection
Normal
Reduced
Protection
5.2.3 Special days
Special days are periods of time during which the building is used for special purposes
and whose start and duration are known in advance. Such days are especially public
holidays.
The 7-day program can accommodate an additional 24-hour program (special day) as a
special day program. The setting is described in section 5.1 "Time switch".
If the controller (master) is connected to other controllers (slaves) via communication, a
specific 7-day program can be entered as a special day on each controller (slaves).
The time of the special day is predefined by the master and applies to all controllers in
the same holidays / special day zone.
5.2.4 Calendar entry
A maximum of 16 entries can be made. The entries are sorted in chronological order.
Every entry must include:
• Date, year and start time
• Date and end time
• Reason for entry (holidays or special day)
Main menu > … > Holidays/special days
Operating line Range Factory setting
Entry 1… Entry 16
Start / End / Reason
--.-- / --.-- /
Holidays
Annually recurring holidays or special days can be entered by setting an asterisk (*) at
the annual setting.
If 2 entries overlap, special days are given priority over holidays. It is thus possible to
predefine a special day during the holiday period also.
Circulating pump
Legionella function
Settings
Setting values
Priority