Basic Documentation

47/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 5 General functions, fundamentals 2017-09-29
The following combinations are possible:
Entry
Effect
Diagram
Autonomous
The holidays / special day program only acts in its
own heating circuit or DHW and only in the
controller.
The holidays / special day program has no impact
on the holidays / special day zone entered on the
"Communication" menu.
Slave
The holidays / special day program of this heating
circuit or of DHW is not active; a holidays / special
day program selected on the slave will be ignored.
Active is some other holidays / special day
program assigned to the same holidays / special
day zone. This holidays / special day program
must be set as the master holidays / special day
program.
Master
The holidays / special day program is set as the
master. It acts on all internal and external holidays
/ special day programs set as slaves and lying in
the same holidays / special day zone.
3140Z09
Main menu > Commissioning > Communication > Room heating circuit 1 (or 2 or 3)
Main menu > Commissioning > Communication > DHW
Operating line
Range
Factory setting
Holidays/special day operation Autonomous / Slave /
Master
Autonomous
Holidays / special day zone
1…31
1
For details on the settings relating to holidays / special day communication, refer to
chapter 5.2.2 "Holidays ".
5.2.2 Holidays
Holidays are periods of time
during which the building is not occupied
whose start and duration are known in advance
Examples:
Works holidays in commercially used spaces and buildings
School holidays in school buildings
Public holidays
The operating mode to be used during the holiday period can be set separately for
each heating circuit and each DHW heating system. The following operating modes can
be selected for the heating circuits:
Economy
Protection
Following can be selected for DHW heating:
Auto
Normal
Reduced
Protection