Basic Documentation

44/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 5 General functions, fundamentals 2017-09-29
Main menu > Commissioning > Communication > Heating circuit 1 (or 2 or 3)
Operating line
Range
Factory setting
Geographical zone (apartm.)
---- / 1…126
----
Time switch slave (apartm.)
---- / 1…126
----
Main menu > Commissioning > Communication > DHW
Operating line
Range
Factory setting
DHW zone
1…31
1
Time switch operation
Autonomous / Slave /
Master
Autonomous
Time switch slave DHW
1…31
1
For details on settings regarding time switch communication, refer to chapter 15
"Communication".
5.1.2 Entries
For space heating, a specific 24-hour program can be selected for each day:
Main menu > Heating circuit 1 (or 2 or 3) > Time switch 1 (or 2 or 3 )
Operating line
Range
Factory setting
Monday
Comfort / Precomfort /
Economy
From 06:00
Comfort / From
22:00 Economy
up to
Sunday
Comfort / Precomfort /
Economy
From 06:00
Comfort / From
22:00 Economy
Special day
Comfort / Precomfort /
Economy
From 06:00
Comfort / From
22:00 Economy
The times are to be entered with the help of a display (using indicator
):
Tuesday
From Comfort
For DHW heating, a specific 24-hour program can be selected for each day:
Main menu > DHW > DHW time switch
Operating line
Range
Factory setting
Monday
Normal / Reduced From 05:00
Normal
From 22:00
Reduced
up to
Sunday Normal / Reduced From 05:00
Normal
From 22:00
Reduced
Space heating
Note
DHW heating