Basic Documentation

38/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 4 General settings 2017-09-29
4 General settings
4.1 Time of day and date
4.1.1 Operating principle
The controller has a yearly clock with time of day, weekday and date.
The following time formats are available:
Time
format
Date Example
Time of day
Example
24 hours
dd.mm.yyyy
(day.month.year)
31.05.2006
hh:mm
(hours:
minutes)
15:56
am/pm mm/dd/yy
(day/month/year)
05/31/2006
hh:mm am/pm
(hours:
minutes am/pm)
03:56 PM
Main menu > Commissioning > Settings > … or
Main menu > Settings > Device
Operating line
Range
Factory setting
Time format 24 hours / 12 hours
(am/pm)
24 hours
Main menu > Time of day/date
Operating line
Range
Factory setting
Time of day
00:00…23:59
00:00
Date
01.01…31.12
01.01
Year
2000…2100
2000
The change from summertime to wintertime, and vice versa, is made automatically. The
date of the earliest changeover can be readjusted should the relevant regulations
change.
The dates set for the change from wintertime to summertime, and vice versa, ensure
that on the first Sunday after that date, the time of day will change from 02:00
(wintertime) to 03:00 (summertime), and from 03:00 (summertime) to 02:00
(wintertime).
If both dates are set to coincide, summer- / wintertime changeover will be inactive.
Main menu > Time of day/date
Operating line
Range
Factory setting
Summer time start
01.01. …31.12
25.03
Winter time start
01.01. …31.12
25.10
4.1.2 Communication
For the time of day, there are several sources available, depending on the master
clock. This can be entered on the controller. Time of day and date can be exchanged
via bus.
For clock time operation, the following settings can be made:
Autonomous (does not send and does not receive)
Clock time from the bus: Clock time slave (receives the synchronization signal from
the bus)
Clock time to the bus: Clock time master (sends the synchronization signal to the
bus)
Time format
Setting
Summer
- / wintertime
changeover
Setting