Basic Documentation
36/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 3 Commissioning 2017-09-29
3.5 Completing commissioning
If the application is valid, the Commissioning menu can be quit as follows:
1.
Press the ESC button. The display shows a menu with the following information:
Caution!
Plant starts
ESC
OK
2.
Confirm by pr
essing the OK knob. Then, the controller starts with the settings
made; the plant is started up, and the Main menu appears on the display.
Main menu:
Commissioning
Heating circuit 1
Heating circuit 2
Heating circuit 2
3.6 Data backup
When commissioning is completed, the entire commissioning data set (configuration
and all settings) can be saved in the controller. If any time later, an unauthorized
person readjusts important values, this function can be used to restore the correct
controlled state after commissioning.
Main menu > Data backup
Operating line
Adjustable values / display / remarks
Storage date Display of the date on which the
commissioning data set was downloaded to
the controller’s memory
Storage year Display of the year in which the
commissioning date set was downloaded to
the controller’s memory
Main menu > Data backup
Operating line
Adjustable values / display / remarks
Restore Caution!
New configuration
Save Caution!
Stored data will be overwritten.
Displays
Setting