Basic Documentation
31/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 3 Commissioning 2017-09-29
3.2.6 Basic configuration
Configuration of the controller is always started by defining the plant type. Based on the
selected plant type, the required types of extension modules are to be selected and will
be displayed on the following lines:
Main menu > Commissioning > Basic configuration
Operating line
Adjustable values / display / remarks
Plant type
H / H0-1…H6-7
Position 1
--- / RMZ782 / RMZ783 through RMZ789
Position 2
--- / RMZ782 / RMZ783 through RMZ789
Position 3
--- / RMZ782 / RMZ783 through RMZ789
Position 4
--- / RMZ782 / RMZ783 through RMZ789
--- = no module configured
On operating line "Plant type", the plant type is to be entered or will be displayed.
Operating lines Position 1…Position 4 display the type of extension module required. On
these operating lines, the presettings can be changed or complemented. When
changing a predefined extension module, all settings relating to these extension
modules and made via "Extra configuration" must be adapted.
Position 1 Position 2
RMH760B RMZ782B RMZ787
Main menu > Commissioning > Basic configuration
Operating line
Adjustable values / display / remarks
Plant type
Basic type H / H0-1…H6-7
Position 1
RMZ782 (1)
Position 2
RMZ787
When using Position 1 in this example, extension module RMZ782B is selected.
Then, at position 2, module type RMZ787 is selected.
Positions 3 and 4 remain blank. They use setting "---" and are confirmed with the OK
knob, which means that they are left blank.
During
the configuration, the ESC button can be pressed to return to the previous
setting.
Once the configuration is started, it cannot be stopped! Configuration must be
completed until the following message appears:
Caution!
New configuration
ESC
OK
Here, the configuration can be aborted.
Functions can be assigned to additional inputs and outputs via "Extra configuration". If
the maximum number of extension modules does not suffice, parts of the plant must be
wired and configured to a second RMH760B.
Plant type
Position …
Configuration example
Position 1
Position 2
Positions 3 and 4
Additional inputs and
outputs