Building Technologies 15 Communication 2017-09-29
A Logic output signal from a RMH760B (device 1) wants to be available as a release
command for a second device. A release command generated in device 1 is sent as
transmission object via a digital output. Device 2 uses this command to start a
decentralized aggregarte.
In the reverse direction, any operating message in device 2 is sent as a
transmission object via a digital output to device 1, where it is processes accordingly.
The following send and receive zone is configured for the example 2:
RMH760B, device 1
RMH760B, device 2
Value
Terminal Transmission
zone
Terminal Reception zone
N.Q4 1 N.X6 1 Release main
controller (device 2)
Terminal Reception zone Terminal Transmission
zone
N.X4 2 N.Q3 2 Display/operating
notification controller
(device 2)
= Transmit
= Receive
On RMH760B (device 1) following will be configured to send the release command to
the main controller (device 2):
Main menu > Commissioning > Communication > LTE transmission zones
Operating line
Range
Factory setting
N.Q4
1
On RMH760B (device 1) following will be configured to receive the display/operating
notification from the main controller (device 2):
Main menu > Commissioning > Extra configuration > Miscellaneous > Input
Operating line
Range
Factory setting
Display input 1:
N.X4
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line
Range
Factory setting
Display input 1:
Digital
Main menu > Commissioning > Communication > LTE reception zones
Operating line
Range
Factory setting
N.X4
2
On RMH760B (device 2) following will be configured to receive the release command:
Main menu > Commissioning > Communication > LTE reception zones
Operating line
Range
Factory setting
N.X6
1
On RMH760B (device 2) following will be configured to send the display/operating
notificatio nfrom the main controller:
Main menu > Commissioning > Communication > LTE transmission zones
Operating line
Range
Factory setting
N.Q3 2
Example 2
Data exchange concept
Configuration device 1