Basic Documentation
230/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 15 Communication 2017-09-29
Reception zones
Transmission zones
Inputs (N.X1…A9(2).X6)
Inputs (N.X1…A)(2).X6)
Digital outputs (N.Q1…A9(2).Q4)
Analog outputs (N.Y1… A9(2).Y2)
Main menu > Commissioning > Communication > LTE reception zones
Operating line
Range
Factory setting
N.X1…A9(2).X6
---, 1…4095
---
Main menu > Commissioning > Communication > LTE transmission zones
Operating line
Range
Factory setting
N.X1…A9(2).X6
N.Q1…A9(2).Q4
N.Y1… A9(2).Y2
---, 1…4095
---
The temperature value from a sensor is available on RMH760B (device 1). This value
is sent as a transmission object via an analog input and processed by an other
RMH760B (device 2).
The following send and receive zone is configured for the example 1:
RMH760B, device 1
RMH760B, device 2
Value
Terminal Transmission
zone
Terminal Reception
zone
N.X4
1
N.X6
1
Sensor temperature value
= Transmit
= Receive
In RMH760B, device 1, the following is configured:
Main menu > Commissioning > Communication > LTE transmission zones
Operating line
Range
Factory setting
N.X4 1
Main menu > Commissioning > Communication > LTE reception zones
Operating line
Range
Factory setting
N.X6
1
Overview
Setting values
Setting values
Example 1
Data exchange concept
Configuration device 1
Configuration device 2
Configuration diagram