Basic Documentation
213/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 14 Function block faults 2017-09-29
Following can be set for each fault status message:
Main menu > Commissioning > Settings > … or
Main menu > Settings > Faults > Fault input 1 (or 2, 3 or 4)
Operating line
Range
Factory setting
Fault text
Max. 20 characters
[Fault input 1] fault*
Fault status message delay 00.00…59.55 m.s
(minutes.seconds)
00.05 m.s
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
None
Fault priority
Urgent / Not urgent
Not urgent
Effect of fault
No stop / Stop
None
Limit value fault on
0 / 1**
1
Limit value fault off
0 / 1**
0
* Or fault input 2, 3 or 4
** Depending on the input identifier
These settings can only be made if the relevant input has previously been activated via
"Extra configuration".
For more detailed information, refer to section 14.5 " Fault properties".
The text for the fault inputs is predefined as [Fault input 1] fault through [Fault input 4] fault.
The text can be edited.
Signal at the fault
input
3131D31
Fault status
message
Signal delay
The fault status message delay is used to set the period of time to elapse for a fault to
be handled as such.
Parameterization "Stop" at the universal fault inputs means that all function blocks
(boiler, main controller, primary controller, heating circuits, and DHW) will be switched
off by the controller. Frost protection, however, continues to be active.
Number Text Effect
9001
[Fault input 1] fault*
According to the settings
9002
[Fault input 2] fault*
According to the settings
9003
[Fault input 3] fault*
According to the settings
9004
[Fault input 4] fault*
According to the settings
* Factory setting; text is freely editable
The digital fault inputs cannot be monitored. We recommend to use wiring where the
signal drops out when there is a fault pending.
Fault text
Fault status
message delay
Fault effects
Fault status messages
Fault handling