Basic Documentation
197/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 12 Function block meter 2017-09-29
12 Function block meter
12.1 Overview of function block
i i i i
1
2
3
4
Counter
i 1
Meter input 1
i 2
Meter input 2
i 3
Meter input 3
i 4
Meter input 4
12.2 Configuration
The meters are to be activated via "Extra configuration" by assigning a terminal to the
meter input.
Main menu > Commissioning > Extra configuration > Data acquisition > Meter 1 (or 2, 3 or 4)
Operating line Range Factory setting
Input 1 (etc., through Input 4)
--- / RMH760.X3, etc.
---
Displayed unit
Wh / kWh / MWh /
kJ / MJ / GJ /
ml / l / m3 /
Heat cost unit /
No unit / BTU
kWh
Displayed format
0 / 0.0 / 0.00 / 0.000
0
The unit shown can be selected via datapoint Displayed unit.
Datapoint Displayed format defines the number of decimal places.
12.3 Types of meters
The meters are used to acquire consumption values.
Pulses from the following types of meters can be handled:
• Gas meters
• Hot water meters
• Cold water meters
• Electricity meters
The pulse values represent:
• Energy in kJ, MJ, GJ, Wh, kWh and MWh
• Volume in m
3
, l
or ml
• Variables with no unit (max. 3 decimal places)
• Heat cost unit
• BTU (British Thermal Unit)
The pulses are converted to consumption values according to the setting values and
then added; the cumulated values are stored as 15-month values at midnight when the
month changes. The monthly values of the last 15 months will be stored.
Extra configuration
Settings
Displays