Basic Documentation
195/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 11 Logic functions 2017-09-29
Necessary configuration settings
Main menu > Commissioning > Extra configuration > Comparator > Comparator 1...2
Operating line
Adjustable values / Comment
Factory setting
Switching value A N.X6
Switching value B
A3.X3
Comparator relay ---
Time format
h:m, m:s
m:s
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Comparator > Comparator 1...2
Operating line
Range
Factory setting
Limit value on 10 K
Limit value off
5 K
Main menu > Commissioning > Extra configuration > Logic functions > Logic 1
Operating line
Adjustable values
Factory setting
[Logic A] input 1 Comparator 1 (d) ---
[Logic A] input 2
A3.X2
---
[Logic A] input 3 --- ---
[Logic B] input 1
---
---
[Logic B] input 2 --- ---
[Logic A] function
AND
OR
[Logic B] function NOR NOR
[Logic C] function
AND
AND
Logic relay A3.Q3 ---
Operation selector
Ja
Nein
Time format m:s m:s
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Logic functions > Logic 1
Operating line
Range
Factory setting
[Logic A switching value 1] on
1
---
[Logic A switching value 1] off
0
---
[Logic A switching value 2] on
65°C
---
[Logic A switching value 2] off
70°C
---
Main menu > Commissioning > Extra configuration > Logic functions > Logic 2
Operating line
Adjustable values
Factory setting
[Logic A] input 1
Logic 1 (d)
---
[Logic A] input 2
A3.X2
---
[Logic A] input 3
---
---
[Logic B] input 1
---
---
[Logic B] input 2
---
---
[Logic A] function
AND
OR
[Logic B] function
NOR
NOR
[Logic C] function
AND
AND
Logic relay
---
---
Operation selector
Ja
Nein
Time format
m:s
m:s