Basic Documentation

189/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 11 Logic functions 2017-09-29
11.1.10 Notes
There is no hysteresis if with an analog input of the Logic block the switching value is
set to On = switching value Off.
The "Off" state is issued for the entire Logic block if an error occurs at a configured
input.
Logic C is ignored and the signal of Logic A is sent directly to the output if only inputs
are configured with Logic A.
Logic C is ignored and the signal of Logic B is sent directly to the output if only inputs
are configured with Logic B.
The Logic blocks are processed sequentially in accordance with their instance
number, i.e. first Logic 1, then Logic 2 to Logic 4.
The result at Logic block 2 becomes available only upon the next handling cycle if
outputs are looped back, e.g. from the output of Logic block 4 to the input of Logic
block 2.
11.1.11 Application example for storage tank charging
The following application example shows a solution for a self-holding function:
The measured value connected to Logic A input 1 issues the switch-on command
for storage tank charging.
The measured value at Logic B input 1 terminates charging.
Required configuration and setting values:
Operating line Comment
[Logic A] function
OR
[Logic B] function NAND
[Logic C] function
AND
[Logic A switching value 1] on
30 °C
[Logic A switching value 1] off
35 °C
[Logic B switching value 1] on
65 °C
[Logic B switching value 1] off
60 °C
Processing order