Basic Documentation

187/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 11 Logic functions 2017-09-29
Operating line
Range
Factory setting
[Logic B switching value 2] on
Depending on selected type
Type-dependent
[Logic B switching value 2] off
Depending on selected type
Type-dependent
11.1.4 Switch-on/switch-off delay
For the Logic output, a switch-on and switch-off delay can be set.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Logic functions > Logic 1...4
Operating line Range Factory setting
Switch-on delay
00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
Switch-off delay
00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in section 11.1.1
The switch-on delay always acts on the switch-on command; the switch-off delay on the
switch-off command.
11.1.5 Minimum on time
For the Logic output, a min. switch-on time can be set. Thus, the output remains set to
On for the set time when a switch-on command is received.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Logic functions > Logic 1...4
Operating line
Range
Factory setting
On time minimum
00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in section 11.1.1
The minimum on-time always takes effect after a switch-on command.
11.1.6 Minimum off time
The minimum switch-off time prevents aggregates from cycling too frequently.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Logic functions > Logic 1...4
Operating line
Range
Factory setting
Off time minimum 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in section 11.1.1
The minimum switch-off time always takes effect after a switch-off command.
Setting values
Note
Setting values