Basic Documentation

181/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 10 DHW heating 2017-09-29
10.13 Diagnostic values
Main menu > DHW > Inputs/setpoints
Operating line
Adjustable values / display / remarks
Act value prim FT
…°C
Event logger 1
…°C
[DHW primary pump] overload
0 / 1 (1 = overload)
[DHW primary pump B] overload
0 / 1 (1 = overload)
Primary pump flow signal
0 / 1 (1 = flow)
Flow temp sec actual value
…°C
Flow temp sec setpoint
…°C
Flow signal
…°C
[DHW sec pump] overload
0 / 1 (1 = overload)
DHW plant type
0 / 1 (1 = overload)
Secondary pump flow signal
0 / 1 (1 = flow)
Act value strge tank temp top
…°C
Act value strge tank temp bott
…°C
Storage tank temp setpoint
…°C
Actual value return temp
…°C
Return temperature max
…°C
Forced charging
0 / 1 (1 = forced charging input)
Flow temp cons actual value
…°C
Flow temp cons setpoint
…°C
[DHW circ pump] overload
0 / 1 (1 = overload)
[DHW circ pump B] overload
0 / 1 (1 = overload)
Circulating pump flow signal
0 / 1 (1 = flow)
DHW optg mode 0 / 1 (1 = external selection of operating
mode)
Special day input
0 / 1 (1 = Special day input active)
Holiday input
0 / 1 (1 = Holiday input active)
Main menu > DHW > Outputs
Operating line
Adjustable values / display / remarks
Mixing valve position primary
0…100 % (3-position and modulating)
Off / On
Primary pump B
Off / On
Mix valve pos maint sec temp
0…100 % (3-position and modulating)
Secondary pump
Off / On
Secondary pump B
Off / On
Electric immersion heater
Off / On
Mix valve pos consumers
0…100 % (3-position and modulating)
Circulating pump
Off / On
Circulating pump B
Off / On
Legionella function relays
Off / On
Main menu > DHW > Limitations
Operating line
Adjustable values / display / remarks
Charging time max
Inactive / Active
Discharge protection
Inactive / Active
Interval operation circ pump
Inactive / Active
Return temperature max
Inactive / Active
Pulse limitation
Inactive / Active
Inputs / setpoints
Outputs
Limitations