Building Technologies 3 Commissioning 2017-09-29
3 Commissioning
Preparations for using and commissioning the Synco™
700 controllers must be made
by qualified staff who have been appropriately trained by SBT HVAC Products.
3.1 Entering the commissioning mode
During commissioning, both control and the plant’s safety functions remain
deacti
vated!
The relays are deenergized, which means that their normally open contacts are open.
When supplying power to the controller for the first time, the Language menu appears.
Here, the language used for commissioning and operating the plant can be selected.
After the language has been selected and confirmed with the OK knob, the time of day,
date and year can be set in the same way. Then, the Commissioning menu will appear.
The access level is automatically set to Password level.
The Plant type menu offers a number of plant types for selection.
When the controller is commissioned for the first time, follow Installation Instructions
G3133; they are enclosed with the controller.
3.2 Basic configuration
A plant is always configured on the password levels and (district heat
parameters).
Main menu > Commissioning > Basic configuration
Operating line
Adjustable values / display / remarks
Plant type
Basic type H / H0-1…H6-7
Position 1
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
Position 2
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
Position 3
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
Position 4
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
On operating line Plant type, the plant type will be entered or displayed.
On operating lines Position 1 through Position 4, it is selected or displayed which of the
extension modules is required. If an extension module is provided for use with the
selected plant type, it is already preconfigured.
Display of "---" means that no module has been configured.
Plant type
Position