Basic Documentation
175/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 10 DHW heating 2017-09-29
10.11 Auxiliary functions
10.11.1 Text designation for DHW and time switches
Main menu > Commissioning > Settings > … or
Main menu > Settings > DHW
Operating line
Range
Factory setting
DHW
Max. 20 characters
DHW
DHW time switch
Max. 20 characters
DHW time switch
Circ pump time switch Max. 20 characters Circ pump time
switch
The text entered here appears on the Main menu and on the info display in place of the
original text.
10.11.2 Primary flow temperature sensor
With plant types DHW 4 and DHW 5, a primary flow temperature sensor can be
configured as an option.
In that case, mixing valve control with plant type DHW 4 is accomplished via the
primary flow temperature.
If the primary flow temperature sensor is configured, its temperature will be used during
active DHW charging to ensure discharging protection.
The function is to be activated via "Extra configuration":
Main menu > Commissioning > Extra configuration > DHW > Inputs > Primary flow
sensor Assign terminal
There are no settings required.
10.11.3 Circulating pump
A circulating pump can be configured for DHW circulation.
The output is to be activated via "Extra configuration":
Main menu > Commissioning > Extra configuration > DHW > Outputs… > Circulating
pump Assign terminal
Control can take place via a specific time program or depending on user requirements
(DHW time switch). Using setting Acc to DHW time switch, the circulating pump will
run during operating mode "Normal
".
By activating the circulating pump for the period of time the legionella function is
performed, the circulation pipe can also be protected against legionella viruses
For detailed information, refer to subsection 10.6.2 "Sequence of legionella function".
Main menu > Commissioning > Settings > … or
Main menu > Settings > DHW > DHW
Operating line
Range
Factory setting
Operation circulating pump
Time switch / On
Time switch
Circulating pump time switch Acc to circ pump time
switch / Acc to DHW
time switch
Acc to circ pump
time switch
Interval operation circ pump
Yes / No
Yes
External circulating pump
Yes / No
No
Extra configuration
Settings
Extra configuration
Settings