Basic Documentation

143/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 9 Heating circuit control 2017-09-29
Number
Effect
5402
>1 identical geogr zone [1]
Nonurgent message; must be
acknowledged. More than one master in
zone of heating circuit 1
5412
>1 identical geogr zone [2]
Nonurgent message; must be
acknowledged. More than one master in
zone of heating circuit 2
5422
>1 same geogr zone [3]
Nonurgent message; must be
acknowledged. More than one master in
zone of heating circuit 3
Number
Effect
2521
[Heat circuit 1 pump]
overload
Nonurgent message.
Acknowledgement can be selected; factory
setting: "Acknowledge and reset".
No heating circuit stop
2522
[Heat circuit 1 pump B]
overload
Nonurgent message.
Acknowledgement can be selected; factory
setting: "Acknowledge and reset.".
No heating circuit stop
2523
[Heat circuit 1 pump] no
flow
Nonurgent message; must be
acknowledged and reset. No heating circuit
stop
2524
[Heat circuit 1 pump B] no
flow
Nonurgent message; must be
acknowledged and reset. No heating circuit
stop
2525
[Heat circuit 1 pump] fault
Urgent message; must not be
acknowledged. Heating circuit stop
Number Text Effect
2531
[Heat circuit 2 pump]
overload
Nonurgent message.
Acknowledgement can be selected; factory
setting: "Acknowledge and reset.".
No heating circuit stop
2532
[Heat circuit 2 pump B]
overload
Nonurgent message.
Acknowledgement can be selected; factory
setting: "Acknowledge and reset."
No heating circuit stop
2533
[Heat circuit 2 pump] no
flow
Nonurgent message; must be
acknowledged and reset.
No heating circuit stop
2534
[Heat circuit 2 pump B] no
flow
Nonurgent message; must be
acknowledged and reset.
No heating circuit stop
2535
[Heat circuit 2 pump] fault
Urgent message; must not be
acknowledged
Heating circuit stops
Number
Effect
2541
[Heat circuit 3 pump]
overload
Nonurgent message.
Acknowledgement can be selected; factory
setting: "Acknowledge and reset.".
No heating circuit stop
Pump fault in heating
circuit 1
Pump fault in
heating circuit 2
Pump fault in heating
circuit 3