Basic Documentation

14/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 2 Operation 2017-09-29
2 Operation
Synco™
700 devices may only be operated by staff who has been instructed by SBT
HVAC Products or their d
elegates and whose attention has been drawn to potential
risks.
2.1 Operation without operator unit
Without operator unit, the following operating elements on the controller and extension
module can be used:
3140Z02
1
2 3 4
3140Z03
5
Controller
Extension module
1
LED (Run) for indicating the controller’s operating state:
LED lit
Power on, correct use and no fault in the peripheral devices
LED off:
No power or incorrect use / faulty peripheral devices
2
Button
with LED (red) for indicating fault status messages and their
acknowledgement:
LED flashes:
Fault status message ready for acknowledgement
LED lit:
Fault status message still present but not yet reset
LED off:
No fault status message present
Press button:
Acknowledgement of fault or reset
3
Button (Prog) for assigning the device address in KNX system mode (tool required)
4
LED (Prog) for indicating programming:
LED lit:
LED remains lit un
til addressing is completed
5
LED (Run) for monitoring power supply and addressing:
LED lit:
Power on, addressing successful
LED flashes:
Power on, controller has not yet a valid KNX address
LED off:
No power