Basic Documentation

138/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 9 Heating circuit control 2017-09-29
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Mixing circuit controller 1
Operating line
Range
Factory setting
Setp increase mixing valve
0…50 K
10 K
The setpoint increase is used to define by what amount the temperature request (to the
boiler or the primary controller) shall be raised against the flow temperature setpoint.
For detailed information, refer to chapter 15 "Communication".
9.10 Auxiliary functions
9.10.1 Text designation
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3)
Operating line
Range
Factory setting
Heating circuit 1*
Max. 20 characters
Heating circuit 1*
Time switch 1**
Max. 20 characters
Time switch 1**
* Or heating circuit 2 or 3
** Or time switch 2 or 3
The text entered here appears on the menu and on the info display in place of the
original text.
9.10.2 Acquisition of the room temperature
The room temperature is required for the optimization functions and for influencing the
flow temperature setpoint.
The input is to be activated via "Extra configuration":
Main menu > Commissioning > Extra configuration > Heating circuit 1 (or 2 or 3) > Inputs >
Room sensor Assign terminal
A heating circuit can handle a maximum of 2 room temperatures. In that case, it is of no
importance whether the room temperature is acquired locally or via the KNX bus.
The average will be generated from the 2 actual values.
The type of room temperature sensor can be selected:
Example with input terminal RMH760.X4:
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > RMH760.X4 > Type
The following choices are available:
LG-Ni 1000
2 × LG-Ni 1000
T1
Pt1000
DC 0…10 V
A maximum of 2 LG-Ni 1000 sensors can be connected to the same terminal. This
cannot automatically be identified by the controller. For this reason, in that case,
2 × LG-Ni 1000 sensors must be selected when parameterizing the terminal inputs.
Setpoint increase
mixing valve
Extra configuration
Averaging
Type of sensor
Example