Basic Documentation
132/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 9 Heating circuit control 2017-09-29
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Optimizations/influences
Operating line
Range
Factory setting
Early shutdown max
00.00…06.00 h.min
00.00 h.min
Maximum early shutdown limits the extent of maximum forward shift. When choosing
setting "00:00", optimum stop control will be deactivated.
9.7.3 Quick setback and boost heating
The purpose of quick setback is to reach the new setpoint as quickly as possible when
changing the room operating mode.
During the time quick setback is active, the heating circuit pump is deactivated and the
heating circuit’s mixing valve fully closed. The heating circuit remains off until the
required room temperature is reached.
The "Quick setback" function can be deactivated on the service level.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Optimizations/influences
Operating line
Range
Factory setting
Quick setback
Off / On
On
Quick setback is started when the room operating mode changes from Comfort or
Precomfort
to Economy or Protection .
It will be ended when the room temperature has reached the new setpoint or when a
change back to Comfort mode
is made.
If a room temperature sensor is installed, the actual value of the room temperature will
be used for aborting quick setback.
If there is no sensor, the temperature of the room model is used to make the
calculation. In that case, the setback time will depend on the outside temperature and
the building time constant.
The purpose of the "Boost heating" function is to work with shorter heating up times.
During the time boost heating is active, the room temperature setpoint is raised by an
adjustable value.
The room temperature setpoint increase heating due to boost heating and the room
influence produce an increase of the flow temperature setpoint. The larger of the 2
influences will prevail.
Boost heating is activated when a change is made from room operating mode Economy
or Protection
to Comfort or Precomfort and when the room temperature lies
0.25 K or more below the setpoint.
3131D37
TR
TRSetpt
TR
SetptCmf
SetptEco
SetptTR
TR
Room temperature
TRSetpt
Room temperature setpoint
SetptCmf
Setpoint, room operating mode Comfort or Precomfort
SetptEco
Setpoint, room operating mode Economy or Protection
∆SetptTR
Setpoint increase
Settings
Maximum early shutdown
Quick setback
Settings
Room temperature
Boost heating