Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 9 Heating circuit control 2017-09-29
p
Window
100-p
Window
+
+
TOeff
TOstrDmp
TOfil
100
100
TO
τ
Bldg
3131B08
τ
Bldg
For the heating limit, the actual, the composite and the attenuated outside temperature
are considered.
The controller is supplied with the proportion of windows set to 50 % so that the
composite outside temperature represents the mean value of the actual and the filtered
outside temperature.
It is calculated as follows:
TOeff = (0.5 × TO) + (0.5 × TOfil)
0
5
10
15
20
25
TOstrDmp
TOeff
t
3131D23
TO
TO
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Space heating
Operating line
Range
Factory setting
Building time constant
0…200 h
20 h
Main menu > Heating circuit 1 (or 2 or 3) > Heating curve
Operating line
Range
Factory setting
Proportion of windows
0…100 %
50 %
9.5.2 Heating curve
The heating curve is defined by 2 curvepoints:
1
:
At the design temperature
By the outside temperature TODef
A
By the flow temperature SetPTFlDef
B
2
:
At the theoretical heating limit
By the outside temperature TOHi
C
By the flow temperature SetPTFlHi
D
p
Window
= 50%
Settings
Heating curve
Curvepoints