Basic Documentation
115/256
Siemens Modular Heating Controller RMH760B CE1P3133en
Building Technologies 9 Heating circuit control 2017-09-29
The input is to be activated via "Extra configuration":
Main menu > Commissioning > Extra configuration > Heating circuit 1 (or 2 or 3) > Inputs >
Timer function Assign terminal
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Space heating
Operating line
Range
Factory setting
Timer function
0…720 min
60 min
This setting does not apply to the QAW740 room unit; in that case, the setting is to be
made directly on the room unit.
The activated timer can be stopped by changing the room operating mode (e.g. via the
room operation selector).
9.3.5 Room operating mode outputs
Function block outputs "Operating mode R1" and "Operating mode R2" enable the
resulting room operating mode of a heating circuit to be output via one or 2 relays. This
is always possible, even if heating circuit control is not used.
Forwarding the resulting room operating mode from the Qx relay outputs of the
RMH760B to a Synco™200 controller:
G
G0
AC 24 V
G
G0
M D1
N2
3121A05
G
G0
N1
Qx3
Qx4
Qx3
Qx4
M D2
N1
RMH760B
N2
Synco™200 RLU2…
Main menu > Commissioning > Extra configuration > Heating circuit 1 (or 2 or 3) > Outputs
Operating line Adjustable values / display / remarks
Operating mode relay 1
--- / N.Q1…, etc. (only free relays) /
assignment of operating mode relays
Operating mode relay 2
--- / N.Q1…, etc. (only free relays) /
assignment of operating mode relays
On the "Settings" menu, the operating mode relay to be energized can be defined for
each room operating mode.
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Space heating
Operating line
Range
Factory setting
Comfort relay control
--- / R1 / R2 / R1+R2
---
Precomfort relay control
--- / R1 / R2 / R1+R2 ---
Economy relay control
--- / R1 / R2 / R1+R2
R2
Protection relay control
--- / R1 / R2 / R1+R2
R1+R2
The factory setting has been chosen such that the digital outputs can be connected
directly to the digital inputs of the Synco™200 controller.
Extra configuration
Settings
Note on QAW740
Tip
Purpose
Application example
Configuration of both
operating mode relays
Settings
Note on factory setting