Data Sheet for Product

6/10
Building Technologies Data sheet KNX bus CE1N3127en
HVAC Products 18.02.2008
Installation notes
Local regulations on insulation against mains voltage (SELV as per EN 60730)
apply if the bus cable is laid in parallel to lines of a three-phase network
(3 x AC 400 V).
Permissible bus topologies are: Tree, line, and star topologies. These topologies can
be mixed as needed. However, ring topologies are not allowed.
The tree topology is advantageous if a large KNX network must be created.
Tree topology (with stub lines) Line topology (with loops)
N2 N2
N1 N3 N4 N1 N4
N5
N6
N7 N3
KNX TP1KNX TP1
3127Z02
N1…N7 Bus devices
CE+
CE-
CE+
CE-
CE+ CE-
Device with
screw terminals
T-branch with
bus terminal
Device with
spring cage terminals
3127Z06en
CE+ CE- CE-CE+
N1 N2 N5 N6
N7N3
N4 N8
CE+ CE-
N1…N8 Bus devices
Lay bus cables
Bus topologies
A
dvantage:
Tree topology
Branching and
connection variants