During commissioning, set the zone addresses as per the plant functions.
Set the zone addresses in Synco 700 devices via operator units RMZ790 and RMZ791,
and locally via QAX910 for the central apartment unit (Synco living).
The service tool OCI700.1 (part of the ACS7… software package) allows for efficient
zone addressing in complex plants featuring many Synco devices.
You can only assign the group addresses to the group objects (= KNX S-mode data
points) via the ETS3 tool. You can order the ETS3 tool from the KNX Association at
www.knx.org/
See document Y3110 for more information on the KNX S-mode data points.
An individual device name (e.g. plant designation) consisting of max. 21 characters can
be assigned to the Synco devices.
The device name is written to the Synco 700 devices via the operator units RMZ790
and RMZ791 as well as the service tool OCI700.1.
For the central apartment unit (Synco living), write the device name locally at the
QAX910 and via the service tool OCI700.1 to the QAX910.
Technical data
Transmission medium (bus cable) TP (twisted pair)
Baud rate 9.6 kbps
(fixed for TP)
Bus line polarity CE+, CE–
(not interchangeable)
Bus terminating resistor Not required
Communication signal
The communication signal (information) is transferred symmetrically, i.e., as voltage difference between
the two bus lines (and not as a voltage difference to the earthing potential). The sign preceding the
voltage between CE+ and CE– determines signal values 0 and 1.
Cable type 2-wire, stranded (
one wire pair)
or 2x2-wire, stranded
or Spiral quad
Wire diameter Min. 0.8 mm, max. 1.0 mm
Wave resistance (ideal value) 120 Ω at 100 kHz
Line resistance 20 Ω/km to max. 75 Ω/km
Capacity, bus line to bus line Max. 100 pF/m at 800 Hz
Greater values require a proportional
shortage of the perm. cable lengths.
Screens Not required
Synco devices do not have a
connection for bus cable screens
Bus power supply via Synco device with DPSU DC 30 V, 25 mA
Zone addresses,
LTE mode
Group addresses,
S-mode
Device name
KNX bus
KNX bus cable
Bus power supply
© 2003-2008 Siemens Switzerland Ltd
Subject to change