Building Technologies Switching and Monitoring Device RMS705 CE1N3123en
HVAC Products 30 May 2008
General notes
The RMS705 switching and monitoring device is maintenance-free (no battery chan-
ges, no fuses). The unit should only be cleaned with a dry cloth.
The unit cannot be repaired on site.
The RMS705 switching and monitoring device is subject to 2002/96/EEC regulations
(WEEE, Waste of Electrical and Electronic Equipment).
"The device must be disposed of as electronic scrap in compliance with the European
directive 2002/96/EEC (WEEE) and not together with municipal waste. The relevant
national regulations must be observed using the correct disposal channels. Local and
currently valid legislation must be complied with."
Technical data
Rated voltage
Safety extra low-voltage (SELV) / protective extra low-voltage
(PELV) to
Requirements for external safety isolating transformer
(100 % duty, max. 320 VA) to
AC 24 V ± 20 %
HD 384
EN 60 742 / EN 61 558-2-6
Frequency 50 / 60 Hz
Power consumption (without modules) 12 VA
Supply line fusing max. 10 A
Backup of clock 48 h typically, min. 12 h
Number refer to "Type summary"
Sensors
Passive
Active
LG-Ni 1000, T1, Pt 1000
2x LG-Ni 1000 (averaging),
0…1000 ,
DC 0...10 V
Contact sensing
Voltage
Current
DC 15 V
5 mA
Requirements for status contacts
Signal coupling
Type of contact
Insulating strength against mains potential
potential-free
maintained contact
AC 3750 V to EN 60 730
Requirements for impulse contacts
Signal coupling
Type of contact
Mechanical signal source (Reed contact)
Max. pulse frequency
Min. pulse duration
Electronic signal source
Max. pulse frequency
Min. pulse duration
Insulating strength against mains potential
shielded cables recommended
potential-free
impulse contact
25 Hz
20 ms (incl. max. 10 ms bounce time)
100 Hz
5 ms
AC 3750 V to EN 60 730
Perm. resistance
Contacts closed
Contacts open
max. 200 Ω
min. 50 kΩ
Number of positioning and switching outputs refer to "Type summary"
Output voltage DC 0...10 V
Output current
± 1 mA
Max. load continuous short-circuit
External supply line fusing
Non-renewable fuse (slow)
Automatic line cutout
Release characteristic
max. 10 A
max. 13 A
B, C, D to EN 60 898
Relay contacts
Switching voltage
AC current
At 250 V
At 19 V
max. AC 250 V
min. AC 19 V
max. 4 A res., 3 A ind. (cos φ = 0.6)
min. 5 mA
min. 20 mA
Maintenance
Repair
Disposal
Power supply (G, G0)
Functional data
Universal inputs
Measured value inputs (X...)
Status inputs (X...)
Outputs
Positioning outputs Y...
Switching outputs
AC 230 V (Q1x...Q7x)