Mechanical design
The RMS705 switching and monitoring unit consists of insert and terminal base. The
terminal base has 2 terminal levels and carries the connecting elements (electrical and
mechanical) for an extension module. The insert with the printed circuit boards is plug-
ged into the terminal base.
The unit can be mounted on a top hat rail (conforming to EN 60 715-TH35-7.5) or di-
rectly on the wall.
Operation takes place via the plug-in type or detached operator unit (refer to section
"Accessories").
3123Z05
1
23
45 67 8 5 109
11
11
1 Connection facility for service tool (RJ45 connector)
2 Removable protective cover with connection facility for operator unit
3 LED "RUN" for indicating the unit’s operating state:
LED on: Power on, use and peripheral devices ok
LED off: No power or wrong use / peripheral devices faulty
4 Button
" " with LED (red) for indicating a fault status message and its acknowledgement:
LED flashing: Fault status message, ready for acknowledgement
LED on: Fault status message still pending but not yet reset
LED off: No fault status message pending
Press button: Acknowledgement or resetting of fault
5 Fixing holes for plug-in type operator unit RMZ790
6 Programming button "Prog": Learning button for changing between normal mode and addressing
mode for adopting the physical device address (tool required)
7 Programming LED "Prog" for indicating "Normal mode" (LED off) or addressing mode (LED on)
for adopting the physical device address
8 Catch for fitting the unit to a top hat rail
9 Fixing facility for a cable tie (cable strain relief)
10 Electrical and mechanical connecting elements for extension module
11 Rest for terminal cover
Engineering notes
• The unit operates on AC 24 V. Operating voltage must conform to the requirements
of SELV/PELV (safety extra low-voltage)
• The transformers used must be safety isolating transformers featuring double
insulation to EN 60 742 or EN 61 558-2-6; they must be suited for 100 % duty
• Fuses, switches, wiring and earthing must be in compliance with local regulations
• Sensor wires should not be run parallel to mains carrying wires that power fans,
actuators, pumps, etc.
• A maximum of 3 extension modules per RMS705 can be connected (possible com-
binations, see chapter “Functions”)