Data Sheet for Product

11 / 16
Siemens REV24.. room temperature controller CE1N2205en
Smart Infrastructure 2019-07-17
Reset
User-defined settings:
Press , and simultaneously for 3 seconds:
This resets all temperature and time settings of the program selection slider to default
values (see also "Factory settings" in the operating instructions). The expert settings
remain unchanged.
The clock starts at 12 p.m., the date on 01-01-08 (01 January 2008).
During the reset, all display fields are lit and can be checked accordingly.
All user-defined settings plus expert settings:
Press the DIP switch reset button
ON
1
3 4
2
2211Z32
5 6
7
8 9
, and simultaneously for 5
seconds:
After the reset, all factor settings are reloaded. This applies to the program selection
slider as well as to the expert settings.
Engineering
· Mount the room temperature controller in the main living room
· Select the mounting place so that the sensor can acquire the air temperature in the
room as accurately as possible and without being influenced by solar radiation or
other heat or refrigeration sources
· Mounting height is approx. 1.5 m above the floor
· You can mount the unit on most commercially available recessed conduit boxes or
directly on the wall
· Begin installation by first attaching and wiring the base. You can mount the base on
most commercially available recessed conduit boxes or directly on the wall. Then
insert the controller from top to bottom into the base.
For more information, see the installation instructions supplied with the unit.
· Comply with all local regulations on electrical installation
· Wire separately the remote control contact T1 / T2 using a separate, shielded cable
Warning!
No internal line protection for supply lines to external consumers.
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
· The power supply line must have an external circuit breaker with a rated current of no
more than 10 A.
Mounting and
installation