3 Notes 
•  The local regulations for electrical installations must be 
complied with 
•  If the reference room is equipped with thermostatic radiator 
valves, they must be set to their fully open position 
•  In the event of a power failure at the REV-R.03/1, the relay will 
be deenergized. 
•  If in normal operation REV-R.03/1 does receive for more than 
25 minutes a very weak or no control telegram from 
REV23.03RF, LED_1 starts to flash in red. 
If control telegram is still understood correctly, receiver 
continues with normal operation. If control telegram is not 
understood anymore, relay remains in last position being 
switched to before. 
As soon as REV-R.03/1 does receive any correct control 
telegram from REV23.03RF again, receiver continuous with 
normal operation 
•  In case of error, REV-R.03/1 switches off relay approximately 
60 minutes after reception of last correct control telegram. 
The controlled device is also switched off and LED_1 flashes 
in red. 
As soon as REV-R.03/1 does receive any correct control 
telegram from REV23.03RF again, receiver continuous with 
normal operation 
Commissioning RF Set
1  Switch on REV23.03RF 
•  Remove the battery transit tab (also refer to Fig. F): As soon 
as the battery transit tab is removed, the unit starts to operate. 
2  Mount REV-R.03/1 temporarly 
•  If possible, mount receiver temporarly in a first run (e.g. double 
coated tape). Doing that, location of best RF reception can be 
identified later on. 
See clause “5 Find location of best reception“ 
•  Completely wire and mount REV-R.03/1 temporarly. Proceed 
according Fig. H to M (please also close front cover) 
3  Link REV-R.03/1 with REV23.03RF 
a)  Switch on power at REV-R.03/1: LED_1 (Fig. H) lights always 
in red or flashes in red 
b)  Press the "RESET“ button on REV-R.03/1 for about 
4 seconds: The orange LED_2 (Fig. H) will flash very fast 
and briefly (stored address of REV23.03RF will be erased) 
c)  Press the "SET“ button (set / learn) for about 3 sec. until the 
orange LED starts flashing slowly and continuously: Receiver 
is now in learning mode 
d)  The receiver stays max. 25 minutes in learning mode. If no 
learning telegram from REV23.03RF is received during that 
period of time, repeat steps b) and c) again 
e)  Press the ESC button 
 on REV23.03RF for about 
4 seconds. Learning telegram is transmitted 
f)  If REV-R.03/1 receives learning telegram, the orange LED_2 
flashes fast and briefly 
g)  If the orange LED_2 is steady on, the relay is energized 
(= controlled device ON) 
h)  If the orange LED_2 is dark, the relay is deenergized 
(= controlled device OFF) 
i)  Depending on the operating state, REV23.03RF repeats the 
ON or OFF control telegram every 3 minutes. With this the 
relay will be switched ON or OFF according to control telegram 
latest after 3 minutes 
j)  If REV-R.03/1 does not receive any correct control telegram 
within 60 minutes, controlled device is being switched off and 
LED_1 flashes in red 
k)  In the event of a power failure at the REV-R.03/1, the relay will 
be deenergized. 
4 Site REV23.03RF 
•  Site REV23.03RF at preferred location for mounting at wall or 
setting up with stand. Remove the unit from its base by 
proceeding according to Fig. A: 
 - for wall mount, refer to Figs. B, C and D 
 - for set up with stand, refer to Fig. E 
•  Also refer to “Mounting and siting notes REV23.03RF and 
REV-R.03/1“ 
5  Find location of best RF reception 
a)  Switch off power at REV-R.03/1 
b)  Switch on REV23.03RF, site at prefered location and press 
override button 
 for about 4 seconds: REV23.03RF 
transmits test telegrams every 2 seconds. Transmission of test 
telegrams stopps automatically after 10 minutes or after 
pressing either “ESC” button or override button 
c)  Switch on power at REV-R.03/1 
d)  Observe both LEDs on REV-R.03/1 from a distance of 
2…3 meters 
e)  Orange LED_2 must flash briefly every 2 seconds. 
Does LED_2 not flash every 2 seconds, distance between 
REV23.03RF and REV-R.03/1 is too far. Mount REV-R.03/1 
closer to REV23.03RF 
f)  LED_1 shows received signal strength of last telegram: 
  LED_1 flashes red:  Signal is too weak to get a durable 
    durable link. Mount REV-R.03/1 
    closer to REV23.03RF 
  LED_1 flashes green:  We distinguish between three 
    signal strenghts: 
    Very good (flashes 3x), 
    Good (flashes 2x) and 
    satisfactory (flashes 1x). 
    As soon as LED_1 flashes in green, 
    link between REV23.03RFand 
    REV-R.03/1 is basically ok. 
g)  Move REV-R.03/1 within an area of approximately 1 square 
meter to find location of best RF reception. Always observe 
LEDs from a distance of 2…3 meters. 
To get a durable link, we recommend to site REV-R.03/1 at 
a location where signal strength is at least “Good”. 
6  Explanation to LED_1 and LED_2 
LED_1 lights always in red: 
No REV23.03RF linked
Red on 
Red off 
LED_1 flashes in red: 
Signal strength too weak
Red on 
Red off
LED_1 flashes 3 times in green: 
Signal strength: Very good 
1 2 3 
LED_1 flashes 2 times in green: 
LED_1 flashes 1 time in green: 
Green on 
Green off 
1 2 3 
Starting 
sequence 
Starting 
sequence 
Signal strength: Good 
1 2 
1 2 
Green on 
Green off 
Starting 
sequence 
Starting 
sequence 
Starting 
sequence 
Signal strength: Satisfactory 
1 
Green on 
Green off 
1 
Starting 
sequence 
1 
Starting 
sequence 
Starting 
sequence 
CE1G2265xx 26.01.2007  7/36 