Technical data
7/17 
Building Technologies  Raumtemperaturregler REV23.03RF  CE1N2265en 
HVAC Products    22.02.2006 
Heating engineer level 
To access the heating engineer level, keep the «Warmer» and «Colder» buttons de-
pressed and simultaneously roll the roller selector away from the display and then to-
ward the display. 
If the displayed temperature does not agree with the room temperature effectively 
measured, the temperature sensor can be recalibrated (recalibration to be made on the 
heating engineer level.) 
The displayed temperature can be matched to the effective room temperature in incre-
ments of 0.2 °C (max. ± 2 °C). 
Minimum setpoint limitation to 16 °C prevents undesired heat transfer to neighboring 
apartments in buildings with several heating zones. The setting is to be made on the 
heating engineer menu. 
Optimization brings forward the switch-on point of the first heating period such that the 
adjusted setpoint will be reached at the required time. 
The setting depends on the type of controlled system, that is, on heat transmission 
(type of piping system, radiators), building dynamics (building mass, insulation), and 
heat output (boiler capacity, flow temperature). 
Optimum start control is switched off at
t
T
17
18
19
- 4
- 2
2264D03
16
- 3
1/4h/°C
1/2h/°C
1h/°C
Start
- 2
- 1
- ½
- 1½
- 1
- ½
- ¼
- ¾
P
on
20
°C
- 1
h 
h 
h
 TR
x
h
h
h
h
h
h
h
h
h
1
st
 heating period
(slow controlled system)
(medium controlled system)
(fast controlled system)
(no impact)
Optimum start controll Off
T
T Temperature (°C)  TR
x
  Actual valve of room temperature 
t  Forward shift of switch-on point (h)  P
on
  Starting point of optimum start control 
REV23.03RF is a 2-position controller providing PID mode. The room temperature is 
controlled by the cyclic switching of an actuating device. 
The controller generates the positioning signals depending on the deviation of the set-
point from the actual value acquired by the built-in temperature sensor. 
The rate of response to the deviation depends on the selected control algorithm: 
The controller is supplied with an active self-learning mode, enabling it to automatically 
adapt to the type of controlled system (building construction, type of radiators, size of 
the rooms, etc.). After a certain learning period, the controller optimizes its parameters 
and then operates with the parameters it has learned. 
PID 12 mode  Switching cycle of 12 minutes for normal or slow controlled systems 
(massive building structures, large spaces, cast-iron radiators, oil 
burners). 
PID 6 mode  Switching cycle of 6 minutes for fast controlled systems (light building 
structures, small spaces, plate radiators or convectors, gas burners). 
2-Pt mode  Pure 2-position control with a switching differential of 0.5 °C (±0.25 °C) 
  for very difficult controlled systems with considerable outdoor tempera-
ture variations. 
For easy commissioning controller is set to 2-Point mode as factory 
setting. 
Access 
Sensor calibration 
CAL 
Setpoint limitation 
Optimum start control 
Example using an actual 
room temperature of 18 °C 
and a setpoint of 20 °C 
Control 
Self-learning mode 










