Technical data
6/17 
Building Technologies  Raumtemperaturregler REV23.03RF  CE1N2265en 
HVAC Products    22.02.2006 
2261Z02
16
 °C
18
20
22
08 10 18 22
 h
Heizphase 1
Heizphase 2
The holiday function is to be selected on the user menu. Set the start of the holiday 
period (day of departure / 
 / weekday), the duration of the holiday period and 
the temperature setpoint (
). This will enable the controller to maintain the adjusted 
temperature for a period of up to 99 days. Every day at midnight, the counter subtracts 
one day. 
When the holiday period is over, the counter reads 00, and the controller will automati-
cally resume the operating mode selected last. 
To be flexible, the REV23.03RF has no connection facility for remote operation. 
  Switching times  Temperatures in ° C 
1st 
period 
2nd 
period
3rd 
period
Oper-
ating 
mode 
Block / 
week-
days
1st period  2nd period  3rd period 
Auto 
1-5 
Mo-Fr 
6-7 
Sa-Su 
06:00 
07:00 
08:00
23:00
11:00 
13:00 
17:00
22:00
19
19
23
23
20
23
21
23
16 
16 
29 
29 
1-7 
Mo-Su 
00:00 24:00        
19 23     
1-7 
Mo-Su 
00:00 24:00        
   16 29    
1-7 
Mo-Su 
00:00 24:00        
   5 35   
1-7 
Mo-Su 
07:00 23:00        
19 23     
Absence      12 30
Setpoint limitation     
Control mode      2-Point control 
Optimum start control  OFF   
Periodic pump run    OFF 
Heating active   
Example with 2 heating 
periods per day 
Holiday function 
Remote operation 
Factory settings 
Factory settings 
Heating engineer level 