Technical data
13/17 
Building Technologies  Raumtemperaturregler REV23.03RF  CE1N2265en 
HVAC Products    22.02.2006 
Technical data controller / transmitter REV23.03RF 
Operating voltage 
DC 3 V 
Batteries (alkaline AA) 
Battery life 
Backup for battery change 
2 x 1.5 V 
approx. 2 years 
max. 1 min 
Sensing element NTC 
Measuring range 
Time constant 
NTC 10 k
Ω at 25 °C ±1 % 
0…50 °C 
max. 10 min 
Setpoint setting ranges 
Normal temperature 
Economy temperature 
5 … 29 °C 
5 … 29 °C 
Frost protection setpoint 
Setting range 
Factory setting 
5...29 °C 
5 °C 
Resolutions of settings and display 
Setpoints 
Switching times 
Measurement of actual value 
Display of actual value 
Display of time 
0.2 °C 
10 min 
0.1 °C 
0.2 °C 
1 min 
SRD band 
Transmit frequency REV23.03RF 
Max. transmitter power 
Max. data throughput 
Modulation 
Frequency stability 
Address range 
(preset in the factory) 
868.7 to 869.2 MHz 
868.95 MHz 
< 10 mW / typically 4 mW 
19200 symbol/s = 38400 Bit/s 
binary frequency changeover BFSK 
< 
±20 ppm (±17 kHz) 
16 Bit (0...65535) 
Operation 
Climatic conditions 
Temperature 
Humidity 
to IEC 60 721-3 
class 3K3 
5...+40 °C 
<85 % r. h. 
Transport 
Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 
to IEC 60 721-3 
class 2K3 
− 25...+70 °C 
<93 % r. h. 
class 2M2 
 conformity 
EMC directive 
R&TTE directive 
89/336/EEC 
EN 301 489-3 
Product safety 
Radio equipment 
EN 301 489-3 
Automatic electrical controls for 
 household and similar use 
EN 60 730-1 
Electromagnetic compatibility 
Immunity 
Emissions 
Radio equipment 
EN 61 000-6-1 
EN 61 000-6-3 
EN 300 220-3 
Approvals 
In the following countries 
 0359 
!
all ECC countries, 
Norway, Iceland and Switzerland 
General data 
controller / transmitter 
General data controller 
General data transmitter 
Environmental 
conditions 
Norms and standards 