Technical data
12/17 
Building Technologies  Raumtemperaturregler REV23.03RF  CE1N2265en 
HVAC Products    22.02.2006 
Reption of control telegram 
a) Switch off power 
b)  Mark location where REV-R.03/1 is currently fixed 
c)  If necessary loosen wiring 
d)  Mount receiver at location marked before, wire completely and close housing 
e)  Switch on mains power 
•  In the event of a power failure at the REV-R.03/1, the relay will be deenergized. 
•  If in normal operation REV-R.03/1 does receive for more than 25 minutes a very 
weak or no control telegram from REV23.03RF, LED_1 starts to flash in red. 
If control telegram is still understood correctly, receiver continues with normal op-
eration. If control telegram is not understood anymore, relay remains in last position 
being switched to before. 
As soon as REV-R.03/1 does receive any correct control telegram from 
REV23.03RF again, receiver continuous with normal operation 
•  In case of error, REV-R.03/1 switches off relay approximately 60 minutes after re-
ception of last correct control telegram. The controlled device is also switched off 
and LED_1 flashes in red. 
As soon as REV-R.03/1 does receive any correct control telegram from 
REV23.03RF again, receiver continuous with normal operation 
•  If instead of REV23.03RF the previous model REV23RF shall be linked with 
REV-R.03/1, follow the procedure below: 
−  Follow steps 1 … 3b (same as commissioning with REV23.03RF) 
−  Instead of step 3c, press buttons SET and RESET simultaneously for approximately 
3 seconds until orange LED_2 starts flashing slowly and continuously: Receiver is 
now in learning mode for previous controller type REV23RF 
−  Change temperature setpoints at REV23RF to force transmission of a control tele-
gram: As soon as orange LED_2 flashes fast and shortly REV23RF and REV-R.03/1 
are linked together 
−  If the orange LED_2 is steady on, the relay is energized (= controlled device ON) 
−  If the orange LED_2 is dark, the relay is deenergized (= controlled device OFF) 
−  Continue to step 7 
LED_2 is always off 
LED_2 is always on 
LED_2 flashes always 
LED_2 flashes briefly 
7. Finishing  
 mounting of  
 REV-R.03/1 
Notes 
Commissioning 
controller/transmitter 
REV23RF 
(previous model) 
and receiver 
REV-R.03/1 
Orange on 
Orange off 
Controlled device OFF
Orange on 
Orange off 
Controlled device ON
Orange on 
Orange off 
Learning mode active