Technical data

9/15
Building Technologies REV200…RF room temperature controller CE1N2214en
HVAC Products 28.08.2008
Remove the battery transit tab: As soon as the battery transit tab is removed, the
unit starts to operate.
If possible, mount receiver temporarily in a first run (e.g. double coated tape). Doing
that, location of best RF reception can be identified later on. See clause “5 Find
location of best reception“
Completely wire and mount REV-R… temporarily (please also close front cover)
a) Switch on power at REV-R…: LED_1 lights always in red or flashes in red
b) Press the "RESET“ button on REV-R… for about 4 seconds: The orange LED_2
will flash very fast and briefly (stored address of REV200… will be erased)
c) Press the "SET“ button on REV-R… (set / learn) for about 3 sec. until the orange
LED_2 starts flashing slowly and continuously: Receiver is now in learning mode
d) The REV-R… stays max. 25 minutes in learning mode. If no learning telegram from
REV200… is received during that period of time, repeat steps b) and c) again
e) Press the “LEARN” button on REV200… for about 4 seconds. Learning telegram is
transmitted
f) If REV-R… receives learning telegram, the orange LED_2 flashes fast and briefly
g) If the orange LED_2 is steady on, the relay is energized (= controlled device ON)
h) If the orange LED_2 is dark, the relay is deenergized (= controlled device OFF)
i) Depending on the operating state, REV200… repeats the ON or OFF control
telegram every 3 minutes. With this the relay will be switched ON or OFF according
to control telegram latest after 3 minutes
j) If REV-R… does not receive any correct control telegram within 60 minutes from
REV200…, controlled device is being switched off and LED_1 flashes in red
k) In the event of a power failure at the REV-R…, the relay will be deenergized.
Site REV200… at preferred location for mounting at wall or setting up with stand
Also refer to “Mounting and siting notes REV200… and REV-R…“
a) Switch off power at REV-R…
b) Switch on REV200…, site at preferred location and press the “TEST” button
for
about 4 seconds: REV200… transmits test telegrams every 2 seconds.
Transmission of test telegrams stops automatically after 10 minutes or after
pressing “TEST” button.
c) Switch on power at REV-R…
d) Observe both LEDs on REV-R… from a distance of 2…3 meters
e) Orange LED_2 must flash briefly every 2 seconds. If LED_2 does not flash every
2 seconds, distance between REV200… and REV-R… is too far. Mount
REV-R… closer to REV200…
f) LED_1 shows received signal strength of last telegram:
LED_1 flashes red: Signal is too weak to get a durable link. Mount REV-R…
closer to REV200…
Commissioning
controller/transmitter
REV200…
and receiver
REV-R.03/1
REV-R.03S/1
1. Switch on
REV200…
2. Mount REV-R.03/1
REV-R.03S/1
temporarily
3. Link REV-R…
with REV200…
4. Site REV200…
5. Find location of
best RF reception
Test telegram
Learning telegram
LED_1 (green / red):
Indication for
- Signal strength
- Receiver linked to
cotroller/transmitter
LED_2 (orange):
Indication for
- Learning mode
- Telegram reception
- Status of relais contact
SET button
RESET button