Technical data

2/15
Building Technologies REV200…RF room temperature controller CE1N2214en
HVAC Products 28.08.2008
Functions
Radio signal transmission
PID control with a self-learning or selectable switching cycle
Automatic operation with 7-day program
3 different 24-hour modes
Remote control and override button
Sensor calibration, reset function
Locking of display to facilitate cleaning and to prevent tampering
Frost protection function, minimum limitation of the setpoint
Holiday mode
Cooling
Pump kick
Optimum start for the first heating period (P.1)
Type summary
Radio signal equipment consisting of:
Room temperature controller (transmitter), receiver
(switching unit) and support
REV200RF/SET
REV200SRF/SET
Room temperature controller (transmitter) and support
REV200.03RF
REV200S.03RF
Receiver (switching unit)
REV-R.03/1
REV-R.03S/1
Ordering
Room temperature controller with 7-day program REV200RF/SET
REV200SRF/SET
When ordering, please give type reference according to
"Type summary". The unit is supplied complete with batteries.
Technical features
The REV200… is a 2-position controller providing PID mode. The room temperature is
controlled by the cyclic switching of a regulating unit.
The control generates the positioning signals according to the deviation of the adjusted
setpoint from the actual value acquired by the built-in temperature sensing element.
The rate of response of the plant depends on the selected control algorithm:
The factory settings produce a self-learning operating mode. The controller adapts
automatically to the type of controlled system (that is, type of building construction, heat
demand, types of radiators, size of rooms, etc.). After a certain learning period, the
controller optimizes its parameters and then operates in the mode it has learned.
In exceptional cases where the self-learning mode may not be adequate, it is possible
to select PID 12, PID 6 or 2-Pt mode:
PID 12 mode Switching cycle of 12 minutes for normal or slow controlled systems
(e.g. massive building structures, large spaces, cast-iron radiators, oil
burners).
PID 6 mode Switching cycle of 6 minutes for fast controlled systems (e.g. light
building structures, small spaces, plate radiators or convectors, gas
burners).
Control
Self-learning mode
Control algorithm