Technical data

12/15
Building Technologies REV200…RF room temperature controller CE1N2214en
HVAC Products 28.08.2008
Technical data REV200…RF
Operating voltage
Batteries (alkaline AA) 2 x 1.5 V
Life
Backup for battery change
DC 3 V
2 x 1.5 V
approx. 2 years
max. 1 min
Sensing element
Measurement range
Time constant
NTC 50 kΩ ±2 % at 25 °C
0…40 °C
max. 10 min
Setpoint setting ranges
Normal temperature
Economy temperature
Frost protection temperature
3…29 °C
3…29 °C
3...16 °C
Resolutions of settings and displays
Setpoints
Switching times
Measurement of actual value
Display of actual value
Display of time
0.2 °C
10 min
0.1 °C
0.2 °C
1 min
SRD band
Transmit frequency REV200…RF
Max. transmitter power
Max. data throughput
Modulation
Frequency stability
Address range (preset in the factory)
868.7 to 869.2 MHz
868.95 MHz
< 10 mW / typically 4 mW
19200 symbol/s = 38400 Bit/s
binary frequency changeover BFSK
<
±20 ppm (±17 kHz)
16 Bit (0...65535)
conformity
Electromagnetic compatibility
Low voltage directive
R&TTE directive
89/336/EEC
2006/95/EEC
EN 301 489-3
Product safety
Radio equipment
EN 301 489-3
EMC directive
Electromagnetic immunity
Electromagnetic emissions
Radio equipment
EN 61000-6-2
EN 61000-6-3
EN 300 220-3
Approvals
In the following countries
0359
!
All ECC countries,
Norway, Iceland and Switzerland
Safety class II to EN 60 730-1
Degree of protection IP30 to EN 60 529
Perm. ambient temperature
Operation
Storage and transport
3...35 °C
-25..+60 °C
Perm. ambient humidity G to DIN 40 040
REV200.03RF incl. packing 0,42 kg
REV200RF/SET incl. packing 0,74 kg
Housing REV200.03RF signal-white RAL9003
Base REV200.03RF grey RAL7038
Housing and base REV200S.03RF silver RAL 9006
Housing 130 x 110 x 33 mm
General unit data
General data
transmitter
Standards
Environmental
conditions
Weight
Color
Seize